This detailed comparison table showcases the most commonly used expansion valves from top HVAC brands Danfoss (TN2, TX2, TS2) and Honeywell (TI Series). Each entry includes the valve series, orifice size, and cooling capacities in both kW and Tons, making it easy to select the ideal valve for your refrigeration or air conditioning system. These thermostatic expansion valves (TXVs) are widely used in split AC units, chillers, cold rooms, and commercial refrigeration systems across the UAE, including Dubai, Abu Dhabi, and Sharjah.
Whether you’re replacing an existing unit or upgrading for performance, this guide helps ensure the right capacity match based on your system’s load and refrigerant specs. Ideal for HVAC technicians, cold chain contractors, and equipment distributors.
Valve Series | Orifice Size | Capacity (kW) | Capacity (Tons) |
TN 2 / TEN 2 | 0X | 0.4 | 0.11 |
TN 2 / TEN 2 | 0 | 0.9 | 0.25 |
TN 2 / TEN 2 | 1 | 1.8 | 0.5 |
TN 2 / TEN 2 | 2 | 2.6 | 0.8 |
TN 2 / TEN 2 | 3 | 4.6 | 1.3 |
TN 2 / TEN 2 | 4 | 6.7 | 1.9 |
TN 2 / TEN 2 | 5 | 8.6 | 2.5 |
TN 2 / TEN 2 | 6 | 10.5 | 3 |
TX 2 / TEX 2 | 0X | 0.5 | 0.15 |
TX 2 / TEX 2 | 0 | 1 | 0.3 |
TX 2 / TEX 2 | 1 | 2.5 | 0.7 |
TX 2 / TEX 2 | 2 | 3.5 | 1 |
TX 2 / TEX 2 | 3 | 5.2 | 1.5 |
TX 2 / TEX 2 | 4 | 8 | 2.3 |
TX 2 / TEX 2 | 5 | 10.5 | 3 |
TX 2 / TEX 2 | 6 | 15.5 | 4.5 |
TS 2 / TES 2 | 0X | 0.38 | 0.11 |
TS 2 / TES 2 | 0 | 0.7 | 0.21 |
TS 2 / TES 2 | 1 | 1.6 | 0.45 |
TS 2 / TES 2 | 2 | 2.1 | 0.6 |
TS 2 / TES 2 | 3 | 4.2 | 1.2 |
TS 2 / TES 2 | 4 | 6 | 1.7 |
TS 2 / TES 2 | 5 | 7.7 | 2.2 |
TS 2 / TES 2 | 6 | 9.1 | 2.6 |
TI-MW / TIE-MW / TIS-MW / TISE-MW | 0 | 0.3 | 0.09 |
TI-MW / TIE-MW / TIS-MW / TISE-MW | 0 | 0.8 | 0.23 |
TI-MW / TIE-MW / TIS-MW / TISE-MW | 1 | 1.9 | 0.54 |
TI-MW / TIE-MW / TIS-MW / TISE-MW | 2 | 3.1 | 0.88 |
TI-MW / TIE-MW / TIS-MW / TISE-MW | 3 | 5 | 1.42 |
TI-MW / TIE-MW / TIS-MW / TISE-MW | 4 | 8.3 | 2.36 |
TI-MW / TIE-MW / TIS-MW / TISE-MW | 5 | 10.1 | 2.88 |
TI-MW / TIE-MW / TIS-MW / TISE-MW | 6 | 11.7 | 3.33 |